Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/11/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE INSTALL OF WATER HEATER AND CALL BACK FOR INSPECTION 2. PSI TEST OK |
|
| 10/01/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS LINE COVERED WITHOUT APPROVAL - REQUIRE CLEAN FILL 2. GAS REQUIRES 12" OF COVER AT ALL POINTS 3. GAS PIPING PASSING THRU EXTERIOR WALLS TO BE PROTECTED, AND ANNULAR SPACE FILLED IN 4. ALL MARRED PIPING TO BE PRIMED AND PROPERLY TAPED 5. ALL VALVES TO BE AGA OR CSA APPROVED 6. T&P RELIEF DRAIN NOT APPROVED 7. SEE 508.3 2006 UPC WATER HEATER SUPPORT 8. NO SEDIMENT TRAP INSTALLED AT WATER HEATER 9. PROVIDE ACCESS TO ALL AREAS 10. SHUT OFF VALVE FOR WATER HEATER TO BE ACCESSIBLE 11. LIST MAY NOT BE COMPLETE CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE |
|
| 07/05/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE 12" OF COVER UNDERGROUND GAS PIPING 2. PROVIDE PROTECTION FOR WATER HEATER 3. PROVIDE APPROVAL T&P PIPING 4. PROVIDE APPROVAL WATER PIPING 5. PROVIDE AGA APPROVAL VALVE AT STOVE 6. PRIMER AND TAPE ALL UNDERGROUND FITTINGS 7. NO UNION UNDERGROUND 8. LIST MAY NOT BE COMPLETE |