Permit: T06PL02306

Parcel: 121112490


Addresses:

4945 E ADAMS ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/19/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12/18/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PIMA/SWAN ENTER OFF OF ARCADIA
NOT 3800 S

1. FLASHINGS REQUIRED AT ROOF PENETRATION
2. LISTED COUPLINGS REQUIRED
3. NEW WH REQUIRES PERMIT AND MUST BE COMPLETE FOR GAS SERVICE.
4. NEW FLEX REQUIRED, T&P REQUIRED TO GRAVITY DRAIN TO EXTERIOR OR PROVIDE A PETITION OF APPEAL AND INSTALL DRAIN PAN AND 125 PSI PRV AT EXTERIOR HOSE BIB.
5. WH AND FURN REQUIRE SEDIMENT TRAPS
6. PROVIDE ELECTRICAL BONDING
7. WRAP TOOL MARKS AND FITTINGS ON SCOTCH-KOTE PIPING BELOW GRADE.