Permit: T06PL02299

Parcel: 134230450


Addresses:

6501 E 12TH ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL02299

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/21/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE TEST ON ENTIRE GAS SYSTEM.
2. SHALL PROVIDE AGA OR CSA APPROVED GAS VALVES
3. SHALL PROVIDE RIDGID NIPPLE THRU FURNACE APPLIANCES HOUSING WITH SEDIMENT TRAP & SEDIMENT TRAP AT WATER HEATER.
4. VENT FROM FURNACE TO HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES FOR DOULBE WALL, 6" CLEARANCE IF SINGLE WALL. DOUBLE WALL THROUGH CEILING & ROOF TO POINT OF TERMINATION WITH APPROVED VENT CAPS. SHALL ALSO APPLY TO WATER HEATER.
5. PROVIDE BONDING OF BUILDING GAS PIPING
TEST ON PIPING FROM NEW METER LOCATION TO STUB UP AT BUILDING SERVICE ENTRY (PARTIAL) SHALL TIE IN & RETEST ENTIRE SYSTEM.