Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/14/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12/13/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTE #3 FROM 12/12/06 INSPECTION MAKE CORRECTION
12/12/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL REMOVE & CAP OLD GAS PIPING SYSTEM AFTER CHANGE OVER.
2. SHALL PROVIDE CORRECT RATED FLEX FOR FURNACES.
1 1/2 FOOT FLEX IS ONLY RATED FOR 93,100 BTU UNIT IS 100,000
3. SHALL PROVIDE APPROVED FULL SIZE DOUBLE WALL VENT PIPING THRU ROOF TO POINT OF TERMINATION MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE
FOR WATER HEATER/FURNACE.