Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/13/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTE #3 FROM 12/12/06 INSPECTION MAKE CORRECTION |
|
| 12/12/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHALL REMOVE & CAP OLD GAS PIPING SYSTEM AFTER CHANGE OVER. 2. SHALL PROVIDE CORRECT RATED FLEX FOR FURNACES. 1 1/2 FOOT FLEX IS ONLY RATED FOR 93,100 BTU UNIT IS 100,000 3. SHALL PROVIDE APPROVED FULL SIZE DOUBLE WALL VENT PIPING THRU ROOF TO POINT OF TERMINATION MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE FOR WATER HEATER/FURNACE. |