Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2006 | PLUMBING - FINAL | Approved | 1. CORRECTIONS MADE OK 2. OK FOR GAS UCC LEFT AT METER SW GAS 889-1888 |
|
| 12/13/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PETITION OF APPEAL #2006-236 ON SITE 1. TEST SHALL HOLD FOR 10 MINUTES WITH NO LOSS OF PRESSURE. 2. PROVIDE NIPPLE WITH NO THREADS IN DISCHARGE END AT 125 # PRESSURE RELIEF DEVICE. 3. SEAL PIPE PENETRATION THRU COMBUSTION AIR INTAKE. |
|
| 12/11/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. T&P SHALL GRAVITY DRAIN TO EXTERIOR OR PROVIDE A PETITION OF APPEAL FROM PERMIT COUNTER. 2. PET. OF A REQUIRES A DRAIN PAN AND EXTERIOR 125 PSI RELIEF VALVE. 3. SECURE WH VENT W/SCREWS 4. PROVIDE ELECTRICAL BONDING 5. PROVIDE SEDIMENT TRAPS AT WH & FURN 6. SUPPORT PIPING ACROSS ROOF AT EVERY 8' AND AT APPLIANCES, USE WEATHER RESISTANT PIPE SUPPORTS AND CLAMPS. 7. DON'T STRAIN PIPING - USE FITTINGS TO OFFSET 8. USE FULL SIZE TEE - 3/4, 1/2 - 1/2 |