Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 12/08/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PRIME ALL JOINTS AND TOOL MARKS BELOW GRADE W/GAS PIPE PRIMER BEFORE WRAPPING PRIMER SHALL BE VISIBLE BEYOND TAPE. 2. REMOVE BRICKS FROM PIPING. 3. GALV 2 HOLE STRAPS ARE APPROVED PIPE SUPPORTS P-TAPE IS NOT 4. WOOD BLOCKS SHALL BE WEATHER RESISTANT 5. WHS INSTALLED OUTSIDE REQUIRE ENCLOSURES. 6. SEDIMENT TRAPS REQUIRED AT WH & FURNACE 7. 1" CLEARANCE AT B VENT 8. EXTERIOR VENT PIPING SHALL BE TYPE B INCLUDING CAP 9. VENTS SHALL NOT REDUCE IN SIZE. 10. PROVIDE COMBUSTION AIR 11. SECURE VENTS W/SCREWS 12. REMOVE FLEX FROM FIRE BOX OF FURN, EXTEND W/NIPP. |