Permit: T06PL02226

Parcel: 125112050


Addresses:

3686 E 3RD ST #05

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/14/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/08/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PRIME ALL JOINTS AND TOOL MARKS BELOW GRADE W/GAS PIPE PRIMER BEFORE WRAPPING PRIMER SHALL BE VISIBLE BEYOND TAPE.
2. REMOVE BRICKS FROM PIPING.
3. GALV 2 HOLE STRAPS ARE APPROVED PIPE SUPPORTS P-TAPE IS NOT
4. WOOD BLOCKS SHALL BE WEATHER RESISTANT
5. WHS INSTALLED OUTSIDE REQUIRE ENCLOSURES.
6. SEDIMENT TRAPS REQUIRED AT WH & FURNACE
7. 1" CLEARANCE AT B VENT
8. EXTERIOR VENT PIPING SHALL BE TYPE B INCLUDING CAP
9. VENTS SHALL NOT REDUCE IN SIZE.
10. PROVIDE COMBUSTION AIR
11. SECURE VENTS W/SCREWS
12. REMOVE FLEX FROM FIRE BOX OF FURN, EXTEND W/NIPP.