Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES FROM 12/11/06 & PAY REFEE COMPLY WITH THESE NOTES THEN CALL FOR REINSPECTION NO FINAL INSPECTION SHALL BE ACHIEVED UNTIL REFEE IS PAID. |
|
| 12/11/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THIS YARD WATER IS ONLY 9 1/2" BELOW GRADE 12" IS THE MIN. REQUIRED COVER PROTECTION OF PIPING AND TEMPERATURES ARE THE CONCERNS. 1/2" PIPING EXPOSED OUTSIDE SHALL BE PROTECTED FROM FREEZING. BREAK OFF SCREW ON VAC BREAKER. PROVIDE CLEAN FILL DIRT. REMOVE CHUNKS OVER 3/4" FROM TRENCH. |
|
| 12/08/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* INSIDE OK, WH OK YARD PIPING N/R |