Permit: T06PL02200

Parcel: 121091390

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/05/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
13.7
12/01/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LESS THAN 4 PSI ON 30 PSI GAUGE IS NOT ACCEPTABLE.
A 15 PSI GAUGE WITH 1/10 PSI INCREMENTATION IS REQUIRED BY CODE IN ORDER TO ASSURE LINE TIGHTNESS WITHIN A REASONABLE AMOUNT OF TIME.
2. WH VENT OPENING IS 3" YOU MAY USE A 4" VENT IF YOU USE THE PROPER FITTING B VENT REQUIRES 1" OF CLEARANCE FROM COMBUSTIBLES. SECURE VENT CONNECTORS W/GALV SHEET METAL SCREWS.
3. SEDIMENT TRAP REQUIRED AT WH
4. T&P SHALL BE OPERATIONAL.
5. FUTURE TEES IN GAS SYSTEM ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED ON APPROVED CITY PLAN. PROVIDE PLAN OR REMOVE TEE.
6. IF YOU WILL INSTALL HOSE BIB VACUUM BREAKERS ON YOUR NEW WATER PIPING, I WON'T ASK FOR A PERMIT FOR YOUR WATER REPIPE. ALSO, SECURE WATER PIPING AT WH
11/30/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
TOOL MARKS ON SCOTCH KOTE
WH VENT, T&P TO BE COMPLETE, SEDIMENT TRAP
ELECTRICAL BONDING
TEST GAUGE
GAS TO WH AND STOVE ONLY