Permit: T06PL02185

Parcel: 10607001F


Addresses:

925 W PRINCE RD


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL02185

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/29/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1. TEST IS OK
2. ROOFTOP UNITS ARE NOT IDENTIFIED
3. IT APPEARS THAT A NEW FAV HAS BEEN INSTALLED
4. PLEASE IDENTIFY UNITS FOR 925
5. PLEASE PROVIDE PROOF OF INSPECTION HISTORY FOR NEW FAV IF ASSOCIATED W/THIS SPACE.
6. SEDIMENT TRAP REQUIRED ON NEW UNITS.
7. CONDENSATE SHALL HAVE CORRECT SUPPORT.