Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* GAS ON METER RELOCATION, GAS CARD AT METER, PLUMBER AND SW TO TIE SYSTEM TOGETHER AND VERIFY NO LEAKAGE AT POINT OF CONNECTION. 12 PSI TEST NEW 1" TO EXISTING SERVICE ENTRY & TO NEW ROOFTOP UNIT LOCATION OK |
|
| 11/30/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1" YARD PIPING TEST FROM NEW METER TO BUILDING EXISTING ENTRY LOCATION IS PARTIAL APPROVAL 13 PSI TEST PENDING RETEST FOR NOTE #1. 1. SHALL COMPLETE PIPING TO NEW ROOFTOP UNIT LOCATION, PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVE & FLEX THAT MEET MINIMUM 100,000 BTU RATING FOR ROOFTOP UNIT. 2. BONDING OF BUILDING GAS PIPING SHALL BE IN ACCESSIBLE VIEWING LOCATION. 3. YOUR CONNECTION TO EXISTING SHALL REQUIRE ACCESS PANEL FOR UNION OR LEFT-RIGHT NIPPLE & COUPLING CONNECTION. 4. YOUR WATER HEATER NEEDS A COLD WATER INLET SHUT OFF VALVE. 5. WATER HEATER VENT NEEDS TO EXTEND WITH DOUBLE WALL VENT PIPING 1' ABOVE NEW ADDITION ROOF LINE. |
|
| 11/29/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* PROVIDE APPROVED PLANS FOR GAS PIPING. |