Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL02157
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
12/10/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. THIS INSPECTION IS FOR DELTA FOUR REVISION ONLY 2. MAY NOT HAVE TWO TRAPS ON ONE TRAP ARM 3. POINT OF VENT MAY NOT BE BELOW TRAP WEIR 4. WHEN THIS INSPECTION IS APPROVED, IT DOES NOT ABSOLVE CONTRACTOR FROM REQUIREMENTS BY THE BUILDING INSPECTOR REGARDING PLUMBING INSTALLATION. NOTE: WATER HEATER RELOCATE, LIKE MATERIALS, SUPPORT, PROTECTION, ETC. |
|
12/05/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WATER HEATER SHOWN AS "EXISTING" HAS BEEN MOVED FROM THE MEZZANINE. NO ACCESS TO MEZZANINE. 2. NO EXPANSION TANK ON WATER HEATER. 3. INDIRECT WASTE PIPING OVER 5' IN LENGTH TO BE DIRECTLY TRAPPED. 4. AIR GAP MUST BE MAINTAINED AT FLOOR SINK. 5. HAND SINK TO BE DIRECTLY CONNECTED TO SANITARY SEWER. |