Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OK FOR GAS UCC LEFT AT METER SW GAS 889-1888 |
|
| 12/12/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 10 PSI TEST FROM METER ABOVE GRADE OVERHEAD TO WATER HEATER & STOVE ONLY OK 1. SUPPORT & SECURE PIPING AT METER. 2. PROVIDE BONDING WITH BONDING CLAMPS. 3. SUPPORT PIPING ON ROOF WITH PERMANENT SUPPORTS. |
|
| 11/22/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GAS PIPING TO BE SUPPORTED ON WALLS PIPING TO BE SUPPORTED 3 1/2" ABOVE ROOF PENETRATION TO HAVE APPROVED FLASHING GAS VALVES TO BE AGA OR CSA APPROVED BOND GAS AND WATER SEDIMENT TRAP AT WATER HEATER WATER HEATER REQUIRES VENT AND T&P RELIEF DRAIN PVC IS NOT APPROVED MATERIAL FOR INTEROR WATER PIPING. |