Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/01/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 15 PSI TEST OK - GAS FLEX A METER SHALL BE LISTED FOR MOBILE HOME USE. - NEW WATER HEATERS INSTALLED ON PARTIAL BOARD FLOOR SHALL BE INSTALLED IN A METAL PAN W/A DRAIN TO PREVENT WH FROM FALLING THROUGH FLOOR. PROVIDE COMBUSTION AIR OPENING. BLACK IRON IS NOT USED FOR WATER PIPING OR RELIEF VALVE. CORRECT NUMEROUS LEAKS. FLEXES ARE KINKED - REPLACE. INSTALL SEDIMENT TRAP AT WH WH DRAFT CONNECTOR IS FROM OLD WH USE THE ONE THAT CAME W/NEW HEATER OFFSET VENT IF NEEDED TO PROVIDE A SQUARE CONNECTION TO WH - SECURE W/SCREWS. |
|
| 11/29/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REPAIR LEAK ON 3" ABS WASTE PIPING UNDER HOME. 2. ADD WATER HEATER TO YOUR ACTIVITY CARD. 3. RUN T&P FROM WATER HEATER TO DAYLIGHT. 4. INSTALL VALVE ON WATER HEATER COLD SUPPLY. 5. PROVIDE FLEX & AGA VALVE TO HOME. |
|