Permit: T06PL02093

Parcel: 136082150


Addresses:

9412 E 29TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/17/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
11/16/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PET. OF APPEAL 2006.1000
GAS FLEX IS 1/2" OD AND 3/8" ID
USE CORRECT FLEX AT FURNACE
11/15/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- 15 PSI TEST IS OK
- LEFT GAS CARD
- 3/8" I.D X 36" GAS FLEX TO FURNACE NOT ADEQUATE FOR 88,000 BTU
- PROVIDE A PERMIT FOR NEW FURNACE
- RECALL FOR FINAL
- PROVIDE APPROVED PETITION OF APPEAL