Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1. 15 PSI TEST ON PIPING PER APPROVED PLAN IS OK GAS SYSTEM IS CURRENTLY ON, MAKE CORRECTIONS, HAVE REINSPECTION. 2. SHALL SEAL PIPE ENTRY INTO BUILDING. 3. AT CHANGE OVER FOR ADDITION OF THIS GAS SYSTEM SHALL PERM CAP & OR SUPPORT OLD PIPING ON METER YARD AREA. 4. PROVIDE BONDING OF BUILDING GAS PIPING. 5. COMPLETE VENTING REQUIREMENTS FOR ALL GAS APPLIANCES. 6. SUPPORT ROOFTOP GAS PIPING AT NEW ROOFTOP UNIT SHUT OFF VALVE ON THIS SYSTEM. |
|
| 11/28/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE DRAWING FOR GAS PIPING THAT HAVE BEEN APPROVED BY THE CITY. 2. HAVE PLUMBER ON SITE |