Permit: T06PL02026

Parcel: 136244130


Addresses:

6921 E MARY DR


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL02026

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD ON PIPE AT METER
889-1888
12/06/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VENT FROM FURNACE TO BE MADE UP FULL SIZE CORRECTLY ON ROOF MEETING REQUIREMENTS OF NOTE #2 FROM 11/30/06 INSPECTION. (TAPE DOES NOT MEET REQUIREMENT)
2. YOUR TEMPERATURE & PRESSURE RELIEF DRAIN PIPING FROM YOUR WATER HEATER IS PLUGGED. SEE NOTE #3 PROVIDE APPROVED PIPING MATERIAL NO FLEX AND MEET REQUIREMENTS OF NOTE #3 FROM 11/30/06 INSPECTION.
11/30/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE BONDING OF BUILDING GAS PIPING.
2. VENTS FROM WATER HEATER & FURNACE TO BE DOUBLE WALL EXTENDING 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH APPROVED VENT CAPS.
3. WATER HEATER REQUIRES TEMPERATURE & PRESSURE RELIEF (SAFETY DEVICE) GRAVITY DRAIN TO DAYLIGHT.
4. REMOVE DUCT TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION ON FURNACE & PROVIDE 3-GALV SCREWS AT EACH JOINT OF FURNACE & WATER HEATER VENT PIPING.
5. SHALL PROVIDE SEDIMENT TRAPS AT GAS ENTRY TO WATER HEATER & FURNACE.