Permit: T06PL01979

Parcel: 136382090


Addresses:

4625 S GOLDENROD DR

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/22/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 20 PSI TEST FROM METER UNDERGROUND UP AT BLDG OVER HEAD TO FURNACE/WATER HEATER ONLY
2) GAS CARD AT METER
11/07/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- EXISTING GAS PIPE IN GROUND NOT APPROVED MATERIAL.
- NEED TO SEE ENTIRE SYSTEM TESTED.
- EXTEND GAS LINE DOWN TO FURNACE.
- PROVIDE APPROVED GAS SHUT OFF VALVES AT APPLIANCES.
- PROVIDE SEDIMENT TRAPS AT FURNACE & WATER HEATER.
- REPLACE DAMAGED 3" DOUBLE WALL PIPE FROM WATER HEATER.
- EXTEND FURNACE & WATER HEATER VENTS MIN. 2' ABOVE EVAP. COOLER.

RECALL FOR INSPECTION.