Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALL IN ALL INSPECTIONS AS REQUESTED BREAK OFF TAMPER SCREW ON HOSE BIB. |
|
| 10/31/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALL IN INSPECTION FOR #T06PL01917 GAS PIPING, #T06PL01939 WATER HEATER AND THIS PERMIT AT SAME TIME. 1. PROVIDE CORRECT VENT CONNECTION FOR SINGLE TO DOUBLE WALL AT WATER HEATER. WITH 3-GALV SCREWS AT EACH JOINT OF VENT FOR WATER HEATER/FURNACE. 2. PROVIDE PLUG IN WATER HEATER DRAIN PAN. 3. PROVIDE NIPPLE WITH NO THREADS ON DISCHARGE END OF 125# PRESSURE RELIEF. 4. PROVIDE VACUUM BREAKER ON NEW HOSE BIB. 5. PROVIDE UPPER COMBUSTION AIR MINIMUM 100 SQ. INCHES FOR WATER HEATER. 6. VENT FROM FURNACE TO BE MINIMUM 2' ABOVE COMBUSTION AIR INTAKE. 7. VENT FROM WATER HEATER TO BE MINIMUM 2' ABOVE TO COMBUSTION AIR INTAKE WITH APPROVED DOUBLE WALL VENT PIPE THRU CEILING & ROOF & APPROVED VENT CAP. |