Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* PETITION OF APPEAL #207 ON SITE |
|
| 11/03/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE NIPPLE WITH NO THREADS ON DISCHARGE END OF 125# PRESSURE RELIEF. 2. BREAK OFF TAMPER SCREW ON NEW HOSE BIB. 3. PROVIDE 125# PRESSURE RELIEF AT EXTERIOR NOT 150# 4. VENTS FROM WATER HEATER & FURNACE TO HAVE 3-GALV SCREWS AT EACH JOINT BE MADE UP CORRECTLY AND TERMINATE 2' MINIMUM ABOVE COMBUSTION AIR INTAKE OR COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH DOUBLE WALL VENT PIPE & APPROVED VENT CAP. 5. PLUG DRAIN PAN DRAIN 6. PROVIDE UPPER COMBUSTION AIR OF 100 SQ. INCHES FOR WATER HEATER. CALL IN ALL INSPECTIONS T06PL01939, T06PL01945, T06PL01917 AS REQUESTED ON INSPECTION SHEETS ALL HAVE NOTES TO BE COMPLIED WITH. PLEASE READ AND COMPLY WITH ALL NOTES ON ALL SHEETS. |
|
| 11/02/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 10:34 NO ACCESS |