Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/01/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. WATER PIPING REQUIRES A MINIMUM OF 12" OF COVER AT ALL POINTS. 2. REMOVE ALL AGGREGATE FROM TRENCH. USE CLEAN FILL AROUND PIPING. 3. SEAL EXTERIOR WALL PENETRATION. 4. ALL EXPOSED EXTERIOR PIPING TO BE INSULATED NO ACCESS TO THE ROOF. 5. HAVE PLAN AND PERMIT ON SITE. |