Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 15 PSI TEST UNDERGROUND TO EXISTING SERVICE ENTRY TO WATER HEATER/FURNACE OK GAS CARD AT METER S.W GAS 889-1888 |
|
| 10/30/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE OR HAVE NEW WATR HEATER ADDED TO PERMIT. 2. REMOVE FUTURE TEE AT EXTERIOR OR PROVIDE CITY APPROVED GAS ISOMETRIC PLAN & RETEST SYSTEM. |
|
| 10/27/2006 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 10/27/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - T&P DRAIN APPEARS TO BE PLUGGED, OR IS NOT OPERATIONAL. - THREAD PROTECTOR AT FURN IS NOT AN APPROVED COUPLING. - SOME SHEETMETAL SCREWS AT B VENT DID NOT PENETRATE VENT CONNECTOR. - REMOVE FUTURE GAS PIPE OR PROVIDE A PLAN, INCLUDE LOCATION OF GRILL ON PLAN. |
|
| 10/25/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION ON WATER HEATER/FURNACE PROVIDE 3-GALV SCREWS AT ALL VENT CONNECTIONS. 2. WATER HEATER T&P TO GRAVITY DRAIN TO DAYLIGHT. 3. PROVIDE SEDIMENT TRAPS AT WATER HEATER/FURNACE GAS ENTRY. 4. PROVIDE APPROVED GAS VALVES FOR ALL APPLIANCES. 5. IF A FUTURE GAS CONNECTION IS DESIRED PROVIDE CITY APPROVED GAS ISOMETRIC. 6. PROVIDE APPROVED COUPLING AT FURNACE GAS ENTRY. 7. SEAL GAS ENTRY INTO BUILDING. |