Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 10/24/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1/2" PIPING TO BBQ PRESSURE TEST OK 1. SHALL TEST THRU LOG LIGHTER VALVE INTO HEARTH OF FIREPLACE. |
|
| 10/20/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WRAP TOOL MARKS ON SCOTCH KOTE 2. EXTEND 3/4 PIPING OVER AND DOWN TO FURNACE. 1/2" PIPING AT 100' IS NOT ADEQUATE FOR 75,000 BTU FURNACE. 3. EXTEND FURNACE FLUE PIPE TO TWO FEET ABOVE FORCED AIR INLET. 4. COMPLETE WH VENT - NO BACKPITCH SECURE EVERY JOINT. |