Permit: T06PL01882

Parcel: 126071320


Addresses:

4026 E ELMWOOD ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/25/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
10/24/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1/2" PIPING TO BBQ PRESSURE TEST OK
1. SHALL TEST THRU LOG LIGHTER VALVE INTO HEARTH OF FIREPLACE.
10/20/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WRAP TOOL MARKS ON SCOTCH KOTE
2. EXTEND 3/4 PIPING OVER AND DOWN TO FURNACE.
1/2" PIPING AT 100' IS NOT ADEQUATE FOR 75,000 BTU FURNACE.
3. EXTEND FURNACE FLUE PIPE TO TWO FEET ABOVE FORCED AIR INLET.
4. COMPLETE WH VENT - NO BACKPITCH SECURE EVERY JOINT.