Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS CARD AT METER |
|
| 10/31/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE ALL NOTES ABOVE FROM 10/25/06 INSPECTION AND COMPLY 1. VENT ON WATER HEATER HAS A HOLE IN FITTING AND SHALL BE REPLACED. |
|
| 10/25/2006 | PLUMBING - FINAL | Not ready for Inspection | WATER HEATER INSTALLED WITHOUT PERMIT OR INSPECTION. 1. SHALL PROVIDE CORRECT VENT CONNECTION FOR WATER HEATER AT SINGLE TO DOUBLE WALL VENT PIPE. 2. FURNACE VENT SHALL VENT AT 1/4" PER FOOT RISE AND BE MADE UP CORRECTLY AT SINGLE TO DOUBLE WALL VENT CONNECTION WITH 3-GALV SCREWS AT EACH JOINT. 3. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN TO DAYLIGHT OR BE INSTALLED PER CITY SIGNED PETITION OF APPEAL FORM FOR ALTERNATE FORM OF T&P RELIEF, PETITION TO BE ON SITE IS OBTAINED AT 201 N. STONE. 4. WATER HEATER & FURNACE REQUIRE SEDIMENT TRAPS AT ENTRY TO APPLIANCES. 5. PLUG TEE AT SERVICE FOR BBQ & RETEST SYSTEM. 6. PROVIDE BONDING OF BUILDING GAS PIPING. |