Permit: T06PL01850

Parcel: 136020060


Addresses:

1531 S PERLMAN AV

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/25/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
TEST FROM METER UNDERGROUND UP AT BUILDING OVERHEAD TO FURNACE/WATER HEATER OK

GAS CARD AT METER SW. GAS 889-1888

1. PROVIDE VACUUM BREAKER ON NEW HOSE BIB & NIPPLE WITH NO THREADS ON DISCHARGE END OF 125# PRESSURE RELIEF.

PETITION OF APPEAL #2006.205 ON SITE
10/23/2006 PLUMBING - FINAL Denied PIPING TO BE SCOTCH COAT TO MINIMUM 6" ABOVE FINISH GRADE OR BE PRIMED & THEN TAPED.
1. SHALL SECURE GAS PIPING AT DROP TO WATER HEATER.
2. SHALL PROVIDE GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN (CANNOT GO UPHILL).
3. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION AND VERIFY MADE UP CORRECTLY WITH 3-GALV SCREWS AT THIS LOCATION OF WATER HEATER VENT AND 3-GALV SCREWS AT THIS LOCATION OF WATER HEATER VENT AND 3-GALV SCREWS AT ALL VENTS REQUIRING SCREWS.
4. SECURE GAS PIPING TO FURNACE CORRECTLY.
5. CAP OLD GAS PIPING PERMANENTLY
6. PROVIDE #4 OR #6 BONDING WIRE.
7. VENTS FROM WATER HEATER & FURNACE TO BE MADE UP CORRECTLY AND TERMINATE MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE.