Permit: T06PL01845

Parcel: 140190080


Addresses:

5344 S PARK AV #67


Inspection Status: Approved

Inspection History: PLUMBING - GAS RECONNECT

Permit Number - T06PL01845

Inspection Description - PLUMBING - GAS RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2006 PLUMBING - GAS RECONNECT Approved IVRS - Inspection :*
GAS CARD ON PIPE AT METER
11/13/2006 PLUMBING - GAS RECONNECT Not ready for Inspection IVRS - Inspection :*
1. PROVIDE GAS PSI TEST ON ALL GAS PIPING
2. LIST MAY NOT BE COMPLETE
10/24/2006 PLUMBING - GAS RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST SHALL HOLD WITH NO PRESSURE LOSS.
SECURE GAS PIPING PROPERLY.

WATER HEATER TO HAVE VENT CONNECTION MADE UP CORRECTLY WITH 3-GALV SCREWS AT EACH JOINT. VENT TO TERMINATE 1' MIN.
WATER HEATER TO HAVE TEMPERATURE & PRESSURE RELIEF DRAIN PIPING INSTALLED, USE APPROVED FULL SIZE PIPING GRAVITY DRAIN TO DAYLIGHT.

NOTE: YOUR FURNACE SHOULD BE SERVICED BY A COMPETENT SERVICE TECHNICIAN PRIOR TO START UP.
10/16/2006 PLUMBING - GAS RECONNECT Not ready for Inspection IVRS - Inspection :*
1. PROVIDE GAS PRESSURE TEST ON ALL GAS PIPING.
2. PROVIDE ACCESS TO WATER HEATER & UNDER MOBILE HOME TO SEE GAS PIPE.
3. LIST MAY NOT BE COMPLETE