Permit: T06PL01820

Parcel: 133290900


Addresses:

8402 E SHILOH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/27/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
11/21/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
3.5 11:16 TEST OK
OK FOR GAS
STILL NEED YOU TO OBTAIN PET. OF APPEAL
REMOVE VALVE ON T&P
10/18/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
4.5 PSI
- BRACE GAS PIPE DROP AT WH, INSTALL SEDIMENT TRAP, AT WH AND FURNACE.
- T&P SHALL GRAVITY DRAIN TO EXTERIOR OR APPLY FOR A PETITION OF APPEAL AT THE PERMIT COUNTER BECAUSE WH IS LOCATED INSIDE HOME. PETITION OF APPEAL REQUIRES THAT A DRAIN PAN BE INSTALLED AND A 125 PSI PRV BE INSTALLED OUTSIDE.
- GAS FLEX CANNOT BE REUSED.
- PROVIDE 2 10X10 COMBUSTION AIR OPENINGS AT WH
- PRIMER AND WRAP TOOL MARKS AND JOINTS W/10 MIL. TAPE
- PROVIDE A FULL SIZE TEE AT BRANCH CONNECTION.
- PROVIDE FLASHINGS AT ROOF PENETRATIONS.
- REMOVE THREAD PROTECTOR COUPLING.