Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 11/21/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 3.5 11:16 TEST OK OK FOR GAS STILL NEED YOU TO OBTAIN PET. OF APPEAL REMOVE VALVE ON T&P |
|
| 10/18/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 4.5 PSI - BRACE GAS PIPE DROP AT WH, INSTALL SEDIMENT TRAP, AT WH AND FURNACE. - T&P SHALL GRAVITY DRAIN TO EXTERIOR OR APPLY FOR A PETITION OF APPEAL AT THE PERMIT COUNTER BECAUSE WH IS LOCATED INSIDE HOME. PETITION OF APPEAL REQUIRES THAT A DRAIN PAN BE INSTALLED AND A 125 PSI PRV BE INSTALLED OUTSIDE. - GAS FLEX CANNOT BE REUSED. - PROVIDE 2 10X10 COMBUSTION AIR OPENINGS AT WH - PRIMER AND WRAP TOOL MARKS AND JOINTS W/10 MIL. TAPE - PROVIDE A FULL SIZE TEE AT BRANCH CONNECTION. - PROVIDE FLASHINGS AT ROOF PENETRATIONS. - REMOVE THREAD PROTECTOR COUPLING. |