Permit: T06PL01717

Parcel: 114610050


Addresses:

260 S PANTANO RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/15/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
04/10/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ADDRESS POSTED
09/29/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ALL ITEMS FROM 9/28/06 INSPECTION
09/28/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SHALL PROVIDE ASME RATED PRESSURE RELIEF FOR POOL HEATER RATED AT 399,000 BTU
SHALL PROVIDE T&P FOR POOL HEATER RATED AT 199,000 BTU
SHALL PROVIDE FLEX RATED FOR ABOVE BTU'S OR HARD PIPE
SUPPORT BRANCH PIPING TO POOL HEATERS.
PROVIDE WORKING T&P DEVICE, GRAVITY DRAIN TO DAYLIGHT FOR WATER HEATER.
PROVIDE FLASHING FOR PENETRATION THROUGH ROOF FOR GAS PIPING TO WATER HEATER RETEST SYSTEM.