Permit: T06PL01702

Parcel: 121111140


Addresses:

4820 E LEE ST


Inspection Status: Partial Approval

Inspection History: SITE - SEWER

Permit Number - T06PL01702

Inspection Description - SITE - SEWER

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/05/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
1) 4 PSI TEST ON PIPING OK
01/30/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
MANHOLE SET, HCS LATERALS INSTALLED
NEED VAC TEST
NEED PIPING TEST
01/26/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
ALL PIPING FROM PRIVATE MANHOLE LOCATION TO PUBLIC MANHOLE LOCATION INSTALLED WITH WYE FITTINGS FOR HCS CONNECTIONS. OK CAP OPEN HCS CONNECTIONS.
WILL TEST AT LATER DATE
HCS FROM PRIVATE MANHOLE TO LOT #5 D.I.P OK
01/24/2007 SITE - SEWER Partial Approval IVRS - Inspection :*
PRE-CON 11 AM SITE SEWER
SHILOH W/STRUNK EXCAVATING 631-3944

WALTER - OWNER REP
BOB - GREGOR ENGINEERING

8" PVC PLANS APPROVED PER 2003 UPC
PRIVATE MANHOLE AND SEWER PIPING FROM PUBLIC MANHOLE TO HAVE CITY INSPECTIONS. TRACER WIRE AND BEDDING/SHADING REQUIRED
ENGINEER WILL VERIFY GRADE AND REDLINE GRADE CHANGES