Permit: T06PL01695

Parcel: 116172330


Addresses:

1026 W COLORADO ST

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/27/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEE NOTE FIVE ABOVE. PLUMBER HAS VALVES ON SITE.
2. BOND SHALL BE #10 COPPER WIRE
3. REMOVE SOILS FROM TRENCH AND SHADE WITH CLEAN FILL.
09/27/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK FOR GAS
SW GAS 889-1888
09/22/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. GAS SYSTEM SHALL BE TESTED IN ITS ENTIRETY.
2. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN TO TERMINATE 6"-24" FROM FINISHED GRADE.
3. WATER HEATER SHALL HAVE WEATHER PROOF ENCLOSURE.
4. VENT FROM WATER HEATER TO BE DOUBLE WALL WHERE IT LEAVES ENCLOSURE, DOUBLE WALL THRU ROOF INSTALLED IN DIRECTION PER MANUFACTURER INSTALLATION INSTRUCTIONS WITH APPROVED VENT CAP. AND SHALL BE MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE.
5. SHALL PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES (AGA OR CSA).
6. REMOVE TAPE AT SINGLE TO DOUBLE WALL VENT CONNECTION FOR FURNACE DRAFT SPACE.
7. PROVIDE BONDING OF BUILDING GAS PIPING.