Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL01683
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* - PIPE SUPPORTS ON ROOF REQUIRE CLAMPS TO KEEP THEM IN PLACE. - ALSO TRIM T&P DRAIN TO TERMINATE 6"-24" ABOVE GROUND - OK FOR GAS AFTER COMPLETING. |
|
| 09/22/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE CLEARANCE AT FLUE PIPE - PROVIDE APPROVED MATERIAL FOR T&P DRAIN (CPVC) AND SOLVENT WELD JOINTS. - ADD SUPPORT ON ROOF AND ON RISER AND ON PIPE TO DRYER -- USE TWO HOLE PIPE CLAMPS OR UNISTRUT CLAMPS. - SEAL WALL PENETRATIONS. |
|
| 09/21/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |