Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/20/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE TAPE AT DRAFT SPACE FROM SINGLE TO DOUBLE WALL VENT CONNECTION. 2. PROVIDE PETITION OF APPEAL FORM FOR ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIFE SIGNED BY CITY ON SITE WITH CORRECT INSTALLATION. 3. T&P DRAIN TO BE 1" ABOVE RIM OF PAN. 4. VENT FROM WATER HEATER TO BE MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' WITH APPROVED DOUBLE WALL VENT PIPE. |