Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EXPOSE ALL PIPING UNDERGROUND FOR VIEWING, SHALL HAVE PRIMER THEN TAPE AT ALL UNDERGROUND FITTINGS. 2. FIREPLACE LOG LIGHTER TO HAVE LOG LIGHTER VALVE WITHIN 4' OF HEARTH IN SAME ROOM AS FIREPLACE & BE TESTED INTO FIREPLACE HEARTH. 3. CAP OLD GAS PIPING THAT IS ABANDONED. 4. WATER HEATER REQUIRES SEDIMENT TRAP. 5. WATER HEATER REQUIRES TEMPERATURE & PRESSURE RELIEF DEVICE GRAVITY DRAIN TO DAYLIGHT OR PETITION OF APPEAL WITH CORRECT INSTALLATION SIGNED BY CITY. 6. VENT FROM WATER HEATER TO BE CORRECT WITH 3-GALV SCREWS AT EACH JOINT. 7. BONDING TO BE TO BUILDING GAS PIPING & COLD WATER PIPING. 8. FURNACE REQUIRES SEDIMENT TRAP AT GAS ENTRY. 9. GAS PIPING TO BE SUPPORTED CORRECTLY ON ROOF. |