Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* INSTALL SEDIMENT TRAP AT FURNACE |
|
| 09/25/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PRESSURE HOLDING STEADY AT 3.8 PSI - EXTEND GAS PIPING AT NEAR METER LOCATION 17" TO POINT OF CONNECTION TO METER. - PLEASE PROVIDE A MIN. 7 1/2 PSI TEST AS SEC. 319.4 LIMITS THE TEST GAUGE TO NOT MORE THAN TWICE THE PRESSURE APPLIED. - SEAL OLD GAS PIPE RISER. - EXTEND VENT CONNECTOR INTO VENT OF FURNACE AND SECURE WITH SCREWS. - PLEASE PROVIDE PROOF OF WH REPLACMENT INSPECTION OR ADD TO THIS PERMIT. |
|
| 09/19/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATE LOCKED ACCESS TO ALL GAS APPLIANCES REQUIRED. |