Permit: T06PL01657

Parcel: 133211140

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/21/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
P OF A #2006.182
09/15/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- 15 PSI GAUGE REQUIRED FOR TEST
- AGA VALVES REQUIRED
- VALVE AT WH NEED TO BE ACCESSIBLE
- INSTALL SEDIMENT TRAPS AT WH AND FURNACE
- T&P DRAIN FROM WH SHALL GRAVITY DRAIN TO EXTERIOR OR PROVIDE A PETITION OF APPEAL FORM AND COMPLY W/REQUIREMENTS OF PETITION OF APPEAL; INSTALL DRAIN PAN ADN 125 PRV.
- WATER HEATER VENT NEEDS TO BE REPLACED W/DOUBLE WALL TYPE B VENT AND TERMINATE 3' ABOVE COOLER.
- PROVIDE ELECTRICAL BONDING OF GAS LINE; GROUND TO WATER PIPE.