Permit: T06PL01654

Parcel: 133300190


Addresses:

8811 E SHILOH PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/19/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
09/18/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
5.9 PSI IS THERE A LEAK?
PROVIDE A TEST PRESSURE THAT IS AT LEAST 1/2 OF GAUGE RANGE.
CORRECTIONS INSIDE OK.
VENT EXTENSIONS SHALL BE TYPE B DOUBLE WALL PIPING
T&P IS DRIPPING
09/15/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE A PRESSURE GAUGE WITH 1/10 PSI INCREMENTATIONS.
- PROVIDE ELECTRICAL BONDING OF GAS LINE
- T&P DRAIN SHALL NOT BE TRAPPED, ENSURE THAT T&P IS OPERATIONAL.
- SECURE VENT PIPE W/GALV SHEET METAL SCREWS AT EACH JOINT
- EXTEND TYPE B VENT TO 3' ABOVE FORCED AIR INLET.
- INSTALL SEDIMENT TRAPS AT FUR AND WH