Permit: T06PL01650

Parcel: 130151400


Addresses:

4502 E 25TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/11/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD AT METER
SW GAS 889-1888
10/09/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN.
2. SUPPORT GAS PIPING AT 8' INTERVALS ALONG WALL.
3. TEST TO BE IN PLACE AT TIME OF INSPECTION 10 PSI MINIMUM WITH NO LOSS OF PRESSURE.
10/03/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- USE SCOTCH COATED PIPE FOR UNDERGROUND SECTIONS & PRIMER & TAPE JOINTS. RETEST SYSTEM.
- T&P DRAIN CANNOT BE REDUCED.
- PROVIDE 3 SCREWS IN EACH JOINT OF WATER HEATER VENT CONNECTORS & CENTER DRAFT DIVERTER.
- 3/8" I.D GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE