Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* OK TO COVER |
|
| 09/13/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOUR REDUCTION OF SIZE AT RP IS IN VIOLATION OF SEC 311.5 - PROVIDE 1" TO SPLIT IN LINE AT BUILDING, TEE INLET SHALL BE FULL SIZE - TRACER WIRE REQUIRED - PIPING SHALL BE INSTALLED IN A MANNER THAT WILL PROVIDE 12" OF COVER ABOVE TOP OF PIPING. |