Permit: T06PL01615

Parcel: 124110680


Addresses:

1641 E MILES ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/30/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
1. UNDER FLOOR FURNACE DISCONNECTED
2. GAS TO WATER HEATER AND STOVE ONLY
3. NOTE: REPLACED WATER HEATER IS LOCATED IN A CLOSET OPENING INTO A BEDROOM. WEATHERSTRIP THE DOOR AND PROVIDE COMBUSTION RELIEF INTO KITCHEN.
4. OK FOR GAS
5. UCC LEFT AT METER.
09/27/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CALLED NUMBER -- NO ANSWER
2. REQUIRE PRESSURE TEST ON ENTIRE GAS SYSTEM. DO NOT TEST THRU APPLIANCES.
3. ALL VALVES TO BE AGA OR CSA APPROVED.
4. PROVIDE ACCESS TO ALL APPLIANCES.
5. NEW WATER HEATER REQUIRES PERMIT AND APPROVED INSTALLATION.
6. REQUIRE BOND BETWEEN GAS AND WATER
7. REQUIRE SEDIMENT TRAPS AT FIXED APPLIANCES
I.E FURNACE
WATER HEATER
09/08/2006 PLUMBING - FINAL Cancelled IVRS - RI canceled