Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. UNDER FLOOR FURNACE DISCONNECTED 2. GAS TO WATER HEATER AND STOVE ONLY 3. NOTE: REPLACED WATER HEATER IS LOCATED IN A CLOSET OPENING INTO A BEDROOM. WEATHERSTRIP THE DOOR AND PROVIDE COMBUSTION RELIEF INTO KITCHEN. 4. OK FOR GAS 5. UCC LEFT AT METER. |
|
| 09/27/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CALLED NUMBER -- NO ANSWER 2. REQUIRE PRESSURE TEST ON ENTIRE GAS SYSTEM. DO NOT TEST THRU APPLIANCES. 3. ALL VALVES TO BE AGA OR CSA APPROVED. 4. PROVIDE ACCESS TO ALL APPLIANCES. 5. NEW WATER HEATER REQUIRES PERMIT AND APPROVED INSTALLATION. 6. REQUIRE BOND BETWEEN GAS AND WATER 7. REQUIRE SEDIMENT TRAPS AT FIXED APPLIANCES I.E FURNACE WATER HEATER |
|
| 09/08/2006 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled |