Permit: T06PL01596

Parcel: 112051280

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T06PL01596

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/08/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/06/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PIPING TO STOVE AND WATER HEATER IS OK.
- REMOVE UNUSED STUB INTO LIVING SPACE AT OLD HEATER LOCATION.
- PROVIDE ELECTRICAL BONDING OF GAS LINE.
- TERMINATE T&P AT 6" ABOVE GRADE.
- PIPE WH FLUE VENT, TYPE B REQUIRED OUTDOORS
- USE BRACKET AT EVE TO SECURE PIPE AND PROVIDE 1" CLEARANCE.
- INSTALL SEDIMENT TRAP AT WH