Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK |
|
| 09/12/2006 | PLUMBING - FINAL | Not ready for Inspection | 1. 80 GALLON WATER HEATER INSTALLED 199,000 BTU 2. GAS PIPING TO BE AT LEAST 3 1/2" ABOVE FLOOR AND MAY NOT PASS IN FRONT OF HEATERS. HEATERS MUST BE ABLE TO BE SERVICED, REPAIRED AND OR REPLACED W/O SHUTTING OFF GAS SYSTEM. 3. RECIRC PUMP NOT SUPPORTED ADEQUATELY PIPING NOT SUPPORTED. 4. UNLESS PIPED IN SERIES -- EACH HEATER SUPPLY TO BE EQUI DISTANT FROM SUPPLY TEE. |