Permit: T06PL01544

Parcel: 112040580

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06PL01544

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/01/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
1. CORRECTIONS MADE OK
2. OK FOR GAS
3. UCC LEFT AT METER

SW GAS 889-1888
08/31/2006 PLUMBING - FINAL Cancelled IVRS - RI canceled
08/30/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE A PRESSURE TEST USING A GAUGE WITH 1/10 PSI INCREMENTATION.
- REPLACE VALVE AT WH WITH AGA VALVE
- TERMINATE T&P TO BUILDING EXTERIOR - TERMINATE 6-24" ABV GROUND W/OUT THREADS.
- SECURE GAS PIPING ON WALL
- SEDIMENT TRAPS REQUIRED AT WH & FURNACE
- ELECTRICAL BONDING
- FLEX W/CORRECT BTU RATING AT FURNACE.