Permit: T06PL01529

Parcel: 111031120

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/14/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
09/08/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PRESSURE TEST IS OK
1/4" PLYWOOD IS NOT ADEQUATE FLOORING UNDER WATER HEATER.
DRAIN PAN IS ALSO REQUIRED ON A WOOD SUBFLOOR
PVC IS NOT ACCEPTABLE FOR T&P DRAIN
VENT CONNECTOR IS NOT CONNECTED TO VENT
SECURE W/SCREWS
08/28/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE AN AIR PRESSURE TEST ON ALL GAS PIPING
- APPLIANCES INSIDE HOME ARE OK
- HORIZONTAL PIPING INSTALLED OUTSIDE SHALL BE KEPT
3 1/2" ABOVE GRADE.
- WATER HEATER IS ABOUT TO FALL THROUGH THE FLOOR.
- REPLACE FLOOR, PROVIDE A DRAIN PAN UNDER WH.
- CORRECT WH VENT AND T&P
08/25/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NOBODY HOME