Permit: T06PL01517

Parcel: 131100070


Addresses:

5610 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/07/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
25 PSI TEST FROM METER PER PLAN OK
08/30/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
08/28/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE OR HAVE ADDED TO PERMIT NEW WATER HEATER.
2. WATER HEATER TO BE IN WEATHERPROOF ENCLOSURE.
3. VENT FROM WATER HEATER TO HAVE 1" MINIMUM CLEARANCE FROM ROOF COMBUSTIBLE MATERIAL.
4. PROVIDE BONDING OF BUILDING GAS PIPING.
5. VENTS FROM FURNACE TO BE MADE UP CORRECTLY WITH
3 GALV SCREWS AT EACH JOINT.

RETEST SYSTEM CALL IN FOR INSPECTION.