Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06PL01513
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. OK TO COVER GAS AND WATER 3. WATER HEATER AND FURNACE EXISTING 4. OK FOR GAS. UCC LEFT AT METER (SW GAS 889-1888) |
|
| 09/01/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. 12.11.1.2(A) COVER REQUIREMENTS - I WILL REQUIRE 18" BECAUSE IT IS IN A TRAFFIC AREA. SAME WITH PVC WATER PIPING. 2. 1211.1.6 PIPING UNDER BUILDINGS (PORCHES INCLUDED) EVERYTHING UNDER THE PORCH OVERHANG IS CONSIDERED "UNDER THE BUILDING". |
|
| 08/29/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 15 PSI TEST NOT HOLDING 1. INCORRECT SLEEVING UNDER FRONT PORCH. 2. TAPE & PRIMER ALL TOOL MARKS & BURNT COATING ON GAS PIPE. TAPE & PRIMER EXISTING FITTING AT HOUSE CONNECTION. ALL TAPE MUST BE TIGHT. 3. PIPE NOT RAN IN A STRAIGHT LINE. 4. ADD YARD WATER LINE TO PERMIT. IMPROPER TRANSITION FROM PVC TO COPPER. 5. GAS PIPE TO BE ON A FIRM BED THE ENTIRE LENGTH. 6. NEED ACCESS TO ALL APPLIANCES. |