Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS PIPING TO WATER HEATER, FURNACE AND STOVE ONLY. PIPING TO FIREPLACE HAS BEEN REMOVED. |
|
| 08/15/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PRESSURE SHALL HOLD STEADY W/NO DROP DURING INSPECTION. - GAS PIPING TO FIREPLACE REQUIRES A SHUT OFF VALVE TO BE ACCESSIBLE FROM SAME ROOM, WITHIN 3' OF FIREPLACE. - PROVIDE ELECTRICAL BONDING - TERMINATE T&P 6"-24" ABOVE GROUND. - SECURE FLUE VENT CONNECTOR AT EACH JOINT - PROVIDE SEDIMENT TRAP AT WH AND FURNACE - PROVIDE SUPPORT FOR GAS PIPING TO FURNACE AND VENT OF FURNACE. PLUMBERS TAPE NOT ACCEPTED. |