Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06PL01409

Parcel: 11103118D

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/11/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/08/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1" PE GAS YARD PIPING FROM METER TO A LOCATION NEAR AC UNIT IS HOLDING A 13 PSI AIR TEST.
1. STATE STATUE REQUIRES THAT THE TRACER WIRE FOR GAS PIPING TO BE YELLOW. CORRECT TRACER WIRE BEFORE BACKFILLING.
2. PROVIDE PLAN SHOWING THAT THIS GAS LINE IS FOR FUTURE USE.