Inspection History: PLUMBING - FINAL

Permit Number - T06PL01340

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
08/02/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
YOU ARE REQUIRED TO PROVIDE AN
1. AIR PRESSURE TEST ON GAS PIPING SYSTEM USE A #15 GAUGE WITH 1/10 PSI INCREMENTATION.
2. AGA VALVES ARE REQUIRED AT GAS APPLIANCES
3. GAS PIPING ON ROOF IS NOT SUPPORTED, SUPPORT PIPING W/WEATHER RESISTANT PIPE SUPPORTS.
4. WH FLUE VENT TERMINATION IS AGAINST FURNACE. EXTEND FLUE VENT TO ONE FOOT ABOVE SIDE WALL OF FURNACE/AC UNIT. USE TYPE B VENT.

NOTE: WH APPEARS TO BE ORIGINAL, T&P TERMINATION WILL BE ADDRESSED WHEN WH IS REPLACED.
08/01/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALLED KELLY AT 10:30
NO ANSWER AT DOOR 1045-1057
NO TEST GAUGE AT METER
PRESSURE TEST REQUIRED