Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD AT METER |
|
| 08/17/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE ROOF JACK AT PIPE PENETRATION THRU ROOF. 2. SHALL PROVIDE BONDING OF BUILDING GAS PIPING. 3. CAP OLD GAS PIPING 4. VENT FROM WATER HEATER SHALL TERMINATE MINIMUM 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH DOUBLE WALL VENT PIPE & APPROVED VENT CAP. |