Permit: T06PL01325

Parcel: 122040210


Addresses:

1822 N BELL AV #02

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/02/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
PRESSURE TEST OK
PROVIDE CLEARANCE BETWEEN WH VENT AND WOOD EVE
INSTALL A PIPE SUPPORT ON GAS PIPING TO WH
PIPE IS RESTING ON HOLE IN ENCLOSURE
INSTALL SUPPORT AT STOVE DROP
GAS CARD LEFT
OK FOR GAS BUT RECALL FOR FINAL APPROVAL
07/31/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE HOME
NOTE: WH HAS BEEN RELOCATED AT SOME TIME PRIOR.
18 1/2 PSI ON 30 PSI GAUGE
WH VENT IS REQUIRED TO BE TYPE B DOUBLE WALL OUTSIDE OF ENCLOSURE.
ALSO, SECURE VENT CONNECTOR W/GALV SHEET METAL SCREWS.
CORRECT DRIPPING T&P
PROVIDE ELECTRICAL BONDING OF GAS LINE
SUPPORT PIPING TO W.H
INSTALL SEDIMENT TRAP AT W.H
SEAL WALL PENETRATION AT? (STOVE) SOUTH WALL
PROVIDE ACCESS TO FURNACE FOR INSPECTION.