Permit: T06PL01316

Parcel: 135110380


Addresses:

7550 E 31ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/10/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
GAS CARD ON PIPE AT METER
07/28/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. GAS PIPING CANNOT RUN IN RIGHT OF WAY (ALLEY) IT SHALL GO FROM METER DIRECTLY ONTO PROPERTY.
2. REMOVE TAPE FROM DRAFT SPACE AT SINGLE TO DOUBLE WALL VENT CONNECTION ON WATER HEATER VENT.
3. PROVIDE SEDIMENT TRAPS AT GAS ENTRY TO FURNACE & WATER HEATER.
4. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN TO DAYLIGHT WITH APPROVED MATERIAL (NO FLEX).
5. VENT FROM WATER HEATER TO TERMINATE MINIMUM 2' ABOVE COMBUSTION AIR INTAKE WITH DOUBLE WALL VENT PIPING & CAP.
6. PROVIDE SUPPORT OF WATER HEATER GAS BRANCH ON ROOF AT CHANGE OF DIRECTION.