Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD ON PIPE AT METER |
|
| 07/28/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GAS PIPING CANNOT RUN IN RIGHT OF WAY (ALLEY) IT SHALL GO FROM METER DIRECTLY ONTO PROPERTY. 2. REMOVE TAPE FROM DRAFT SPACE AT SINGLE TO DOUBLE WALL VENT CONNECTION ON WATER HEATER VENT. 3. PROVIDE SEDIMENT TRAPS AT GAS ENTRY TO FURNACE & WATER HEATER. 4. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN TO DAYLIGHT WITH APPROVED MATERIAL (NO FLEX). 5. VENT FROM WATER HEATER TO TERMINATE MINIMUM 2' ABOVE COMBUSTION AIR INTAKE WITH DOUBLE WALL VENT PIPING & CAP. 6. PROVIDE SUPPORT OF WATER HEATER GAS BRANCH ON ROOF AT CHANGE OF DIRECTION. |